1. The top of a drainage stack is extended through the roof as the same pipe. What is this vent called?

  1. A vent stack.
  2. A branch vent.
  3. A relief vent.
  4. A stack vent.

Article 1.4.1.2. of Division A defines a stack vent as the vent pipe that joins the top of a stack to a vent header or to outside air, and Article 2.5.4.1. requires every stack to end in one. A vent stack is a separate pipe tied into the stack at or below its lowest drainage connection. A branch vent joins several vent pipes, and a relief vent works with a circuit vent to add air circulation.

2. A building needs water while its single RP assembly is tested. Which arrangement meets the NPC 2020?

  1. A parallel line with a locked gate valve.
  2. A parallel line with a single check valve.
  3. A parallel line with a second RP assembly.
  4. A parallel line with a dual check valve.

Article 2.6.2.12. of the NPC 2020 does not permit bypass piping or any other device that could reduce the effectiveness of a backflow preventer. A second RP assembly installed in parallel keeps every flow path protected at the same level, so one assembly can be tested while the other supplies the building. A line with a locked gate valve has no protection, and a single check valve or a dual check valve gives weaker protection than the RP assembly, so each of these lines is the kind of bypass the Article prohibits.

3. A UV unit's intensity alarm sounds although the lamp is lit and within its rated life. What is cleaned first?

  1. The lamp's quartz sleeve.
  2. The electronic ballast box.
  3. The inlet check valve.
  4. The outlet sampling tap.

Scale and films on the quartz sleeve cut the UV light reaching the water, which trips the intensity alarm even when the lamp is lit, so the sleeve is cleaned first and the lamp is replaced only at the end of its rated life. A ballast box, a check valve and a sampling tap do not reduce the UV passing through the sleeve.

4. A scissor lift is set up on freshly placed backfill and raised to full height. Which hazard does the soft ground create?

  1. Excessive load on the deck
  2. Pinching at the scissor arms
  3. Tipping of the raised lift
  4. Shock from overhead lines

Freshly placed backfill is soft and can settle unevenly under the wheels, so a lift raised to full height may lean and tip over (sub-task A-2.02 of the RSOS: tipping, uneven surfaces). An excessive load depends on what is placed on the deck, not on the ground below. Pinch points at the scissor arms and shock from overhead lines are real lift hazards, but soft ground does not create them.

5. An NPS 1 steel nipple is threaded with an NPT die. How does the thread seal when the fitting is made up?

  1. A rubber washer seals against the pipe end.
  2. Straight threads bottom against the fitting.
  3. A gasket is crushed between two flat faces.
  4. Tapered threads wedge tight as they engage.

An NPT thread is cut on a taper, so the male and female threads wedge together as the joint is drawn up and, with sealant, close the leak path. A washer or a gasket belongs to other joint types, not to a tapered pipe thread. A straight thread has no wedging action and would not seal by bottoming against the fitting.

6. A plate heat exchanger on hard water shows a rising approach temperature and a falling output. What service restores it?

  1. Raise the boiler supply setpoint.
  2. Add glycol to the primary loop.
  3. Circulate descaler through it.
  4. Replace the loop expansion tank.

Scale from hard water insulates the plates, so heat transfer falls and the approach temperature rises; circulating a descaling solution through the exchanger dissolves the scale and restores the output. A higher setpoint wastes energy and speeds up scaling, glycol does not remove deposits, and the expansion tank has no effect on scale.

7. An upright cylindrical holding tank is 1.6 m in diameter and holds sewage to a depth of 2.0 m. What is the volume of sewage, to the nearest litre?

  1. 1 280 L
  2. 4 021 L
  3. 5 027 L
  4. 16 085 L

The formula sheet gives the volume of a cylinder as π × radius² × height, with π = 3.1416. The radius is 0.8 m, so 3.1416 × 0.64 × 2.0 = 4.021 m³, or 4 021 L. A value of 1 280 L leaves out π, 5 027 L does not square the radius, and 16 085 L uses the diameter as the radius.

8. A roof cistern water level is 55 ft. above a hose bibb. What static pressure acts at the bibb?

  1. 2.4 psi
  2. 23.8 psi
  3. 55.0 psi
  4. 127.0 psi

Static pressure equals height x 0.433 psi/ft. from the formula sheet, so 55 x 0.433 = 23.8 psi. The value of 127.0 psi divides by 0.433, 55.0 psi reads the height as psi, and 2.4 psi shifts the decimal point.

9. A hospital asks to flush its water closets with reclaimed water. What is done?

  1. Supply the closets from the potable system.
  2. Add a pressure-reducing valve to each fixture.
  3. Add a reduced pressure backflow preventer.
  4. Add marked pipe to the closet supplies.

Sentence 2.7.1.1.(3) of the NPC 2020 does not permit a non-potable water system to supply fixtures in healthcare facilities, so the closets stay on the potable system. A pressure-reducing valve (550 kPa limit), a backflow preventer and pipe marking are conditions for permitted systems, but none of them removes the healthcare prohibition.

10. A branch drains a sump pump that discharges 2 L/s continuously and a floor drain with an NPS 2 trap to a sanitary sewer. What is the smallest NPS that Table 2.4.10.6.-B permits?

  1. NPS 1½
  2. NPS 2
  3. NPS 3
  4. NPS 4

Sentence 2.4.10.3.(1) of the NPC 2020 counts 31.7 fixture units for each litre per second of continuous flow, so the pump adds 2 x 31.7 = 63.4, and the floor drain with an NPS 2 trap adds 2 (Table 2.4.9.3.), for 65.4 in total. Table 2.4.10.6.-B limits an NPS 3 branch to 27 fixture units, so NPS 4 (180) is needed. NPS 3 comes from wrongly reading the stack limit of Table 2.4.10.6.-A (102), NPS 2 from counting the pump as only 2 fixture units, and NPS 1½ from dividing 2 by 31.7 instead of multiplying.

11. A softener serves 4 persons who each use 60 gallons per day. Hardness is 18 gpg, the iron concentration to enter in the formula is 2, and regeneration is every 4 days. What capacity is required?

  1. 4,800 grains
  2. 17,280 grains
  3. 19,200 grains
  4. 297,754 grains

Correct answer: “19,200 grains”. The worked calculation, step by step, is included with full access.

12. Which standard governs the installation of a packaged solar domestic hot water system under the NPC 2020?

  1. ANSI/ASSE 1010
  2. CAN/CSA-B356
  3. CAN/CSA-F383
  4. ASME A112.4.14

Correct answer: “CAN/CSA-F383”. The full explanation, with the National Plumbing Code 2020 reference, is included with full access.

13. A cylinder of compressed nitrogen is delivered to the site. Which WHMIS pictogram on its supplier label shows a gas under pressure?

  1. Gas cylinder
  2. Exploding bomb
  3. Health hazard
  4. Exclamation mark

Correct answer: “Gas cylinder”. The full explanation, with the RSOS task it comes from, is included with full access.

14. A 30 m run of PVC drain pipe is installed at 10 °C and later runs at 50 °C. To the nearest mm, how much does it expand?

  1. 21 mm
  2. 40 mm
  3. 71 mm
  4. 119 mm

Correct answer: “71 mm”. The worked calculation, step by step, is included with full access.

15. What is the main purpose of an expansion tank in a closed hydronic heating system?

  1. Remove dissolved air from the water.
  2. Absorb the water's thermal expansion.
  3. Raise the pressure at the boiler outlet.
  4. Reduce the flow through the zone loops.

Correct answer: “Absorb the water's thermal expansion”. The full explanation of why this is right and the other choices are wrong is included with full access.

16. Whatever the pipe size, what is the smallest air break the NPC permits for an indirect connection?

  1. 25 mm
  2. 38 mm
  3. 50 mm
  4. 75 mm

Correct answer: “25 mm”. The full explanation, with the National Plumbing Code 2020 reference, is included with full access.

17. During a municipal sewer surcharge, sewage rises from a basement floor drain below the adjoining street level. What was missing on the fixture drain?

  1. A deep-seal trap on the drain.
  2. A trap seal primer on the drain.
  3. A cleanout plug on the drain.
  4. A backwater valve on the drain.

Correct answer: “A backwater valve on the drain”. The full explanation, with the National Plumbing Code 2020 reference, is included with full access.

18. The maker of an atmospheric vacuum breaker specifies a critical level 75 mm above the flood level rim of a tank. What is the minimum height that applies?

  1. 25 mm
  2. 75 mm
  3. 100 mm
  4. 300 mm

Correct answer: “75 mm”. The full explanation, with the National Plumbing Code 2020 reference, is included with full access.

19. A dishwashing sink is being replaced. Which feature does the NPC prohibit on the new sink?

  1. A concealed overflow.
  2. A standing waste.
  3. A basket strainer.
  4. A separate trap.

Correct answer: “A concealed overflow”. The full explanation, with the National Plumbing Code 2020 reference, is included with full access.

20. A storm building sewer is NPS 6 and is laid at 1 in 133. What maximum hydraulic load does the NPC 2020 table permit?

  1. 10 700 L
  2. 12 400 L
  3. 15 200 L
  4. 17 600 L

Correct answer: “10 700 L”. The full explanation, with the National Plumbing Code 2020 reference, is included with full access.

21. Plastic drain pipe will wait outdoors on site for several weeks before installation. How is it protected from sunlight?

  1. Wrap it in clear plastic film.
  2. Leave it uncovered to stay cool.
  3. Lay it on a dark metal rack.
  4. Cover it with an opaque tarp.

Correct answer: “Cover it with an opaque tarp”. The full explanation, with the RSOS task it comes from, is included with full access.

22. An inspector finds a slip joint in the vent piping of a washroom group. Where does the NPC permit a slip joint?

  1. In the same vent, where it is accessible
  2. At an accessible trap-to-fixture-drain joint
  3. In the same vent, above the flood level rim
  4. In the building drain below the floor

Correct answer: “At an accessible trap-to-fixture-drain joint”. The full explanation, with the National Plumbing Code 2020 reference, is included with full access.

23. A make-up water line feeds a closed hydronic boiler that contains a non-toxic fluid. Which device does the NPC permit on that line against back pressure?

  1. A pressure vacuum breaker assembly.
  2. A dual check valve backflow preventer.
  3. A pressure-reducing valve assembly.
  4. A spring-loaded single check valve.

Correct answer: “A dual check valve backflow preventer”. The full explanation, with the National Plumbing Code 2020 reference, is included with full access.

24. A pump on a 40/60 psi switch cycles every few seconds. With the tank drained, the air valve reads 10 psi. What is the fix?

  1. Replace the foot valve.
  2. Raise the cut-out to 70 psi.
  3. Recharge the tank to 38 psi.
  4. Replace the pressure gauge.

Correct answer: “Recharge the tank to 38 psi”. The full explanation of why this is right and the other choices are wrong is included with full access.

25. Hard water is scaling a storage water heater. Where is the softener piped in relation to the heater?

  1. On the hot water outlet.
  2. On the recirculation return.
  3. On the expansion tank tee.
  4. On the heater's cold feed.

Correct answer: “On the heater's cold feed”. The full explanation of why this is right and the other choices are wrong is included with full access.

26. A vent pipe ends near a roof deck that supports an occupancy. At least how far above that roof must the terminal be?

  1. 1.0 m
  2. 2.0 m
  3. 3.5 m
  4. 4.5 m

Correct answer: “2.0 m”. The full explanation, with the National Plumbing Code 2020 reference, is included with full access.

27. Rust-coloured staining appears at the orbital welds of a new stainless dairy line. What is the likely cause?

  1. The gaskets were the wrong material.
  2. The hangers were spaced too widely.
  3. The welds were not passivated.
  4. The line was pressure tested with air.

Correct answer: “The welds were not passivated”. The full explanation of why this is right and the other choices are wrong is included with full access.

28. A new urinal is specified for a school washroom. What maximum water usage per flush cycle does the NPC 2020 allow?

  1. 1.0 Lpf
  2. 1.9 Lpf
  3. 4.8 Lpf
  4. 6.0 Lpf

Correct answer: “1.9 Lpf”. The full explanation, with the National Plumbing Code 2020 reference, is included with full access.

29. A building sewer backs up repeatedly. A camera shows roots entering at a joint. What service is carried out?

  1. Add strong acid to the cleanout.
  2. Backfill the joint with loose soil.
  3. Close the line at the main cleanout.
  4. Cut the roots and camera-inspect.

Correct answer: “Cut the roots and camera-inspect”. The full explanation of why this is right and the other choices are wrong is included with full access.

30. Which reference gives a fixed elevation for laying out piping levels on site?

  1. A chalk line snapped on the slab.
  2. A plumb bob hung from the joists.
  3. A scale ruler laid on the plan.
  4. A benchmark of known elevation.

Correct answer: “A benchmark of known elevation”. The full explanation, with the RSOS task it comes from, is included with full access.

31. What does roll grooving do to the wall of NPS 4 steel pipe at the groove?

  1. It displaces metal without removing any.
  2. It cuts away a ring of the wall metal.
  3. It thickens the pipe wall at the groove.
  4. It flares the pipe end into a small bell.

Correct answer: “It displaces metal without removing any”. The full explanation of why this is right and the other choices are wrong is included with full access.

32. In mild weather a boiler cycles on and off every few minutes while one small zone calls for heat. What is the most likely cause?

  1. Boiler output exceeds the zone load.
  2. The LWCO probe is coated with scale.
  3. The expansion tank lost its charge.
  4. The high limit is set too high.

Correct answer: “Boiler output exceeds the zone load”. The full explanation of why this is right and the other choices are wrong is included with full access.

33. What is the maximum number of shower heads that one shower drain may serve?

  1. 2 heads
  2. 4 heads
  3. 6 heads
  4. 8 heads

Correct answer: “6 heads”. The full explanation, with the National Plumbing Code 2020 reference, is included with full access.

34. A relief valve discharge pipe ends above a floor drain. What is the maximum air break the NPC 2020 allows?

  1. 300 mm
  2. 450 mm
  3. 600 mm
  4. 900 mm

Correct answer: “300 mm”. The full explanation, with the National Plumbing Code 2020 reference, is included with full access.

35. Which standard must cast-iron frames and covers for maintenance holes and catch basins meet?

  1. CSA B70
  2. CSA B70.1
  3. CSA B181.1
  4. CSA B182.1

Correct answer: “CSA B70.1”. The full explanation, with the National Plumbing Code 2020 reference, is included with full access.