What this topic covers
Major Work Activity E of the RSOS Plumber 2023, fixtures, appliances and water treatment, carries 17 of the 125 exam questions: task E-14, plumbing fixtures and appliances, including water heaters (11); task E-15, water treatment systems (6). These are original practice notes, not Red Seal program documents. Code points are based on the National Plumbing Code of Canada 2020 (NPC 2020), the edition provided at the exam; trade points reflect standard methods and notions of the trade. The exam is open book, so the notes also say where to look in the code.
Installing fixtures
- Showers: one shower drain serves no more than 6 heads (Sentence 2.2.2.3.(2)).
- Public washroom: elongated water closet with an open-front seat (Article 2.2.2.5.).
- Food sinks: no concealed overflow (Article 2.2.2.4.). Urinals not beside pervious walls or floors (Article 2.4.3.1.).
- Drinking fountain: shielded orifice aiming upward at about 45 degrees (Sentence 2.2.10.9.(1)).
- Macerating toilet: only where no gravity drainage connection exists (Article 2.4.3.5.). Wall-hung fixtures need backing set between the studs.
Connections and traps
- Floor flange: brass, or the material of the plastic pipe; sealed with a resilient watertight and gas-tight seal (Sentences 2.3.3.8.(2), (3) and (6)).
- Traps: one per fixture, but one trap may serve a 2-compartment sink or 2 similar fixtures in one room (Article 2.4.5.1.). A dishwasher line rises under the counter and joins the sink trap inlet with a Y (Sentence 2.4.5.1.(6)).
- Outlet size: by discharge in Table 2.4.9.3.; a 9.5 to 20 L/min shower needs NPS 2.
- Flush valve: needs a vacuum breaker unless the fixture prevents back-siphonage (Clause 2.2.10.8.(1)(d)).
Hot water temperatures
- Shower and bathtub: at most 49 °C; 43 °C in healthcare facilities and seniors' residences (Sentences 2.2.10.7.(4) and (5)). Note A-2.2.10.7. explains the limit is set at the automatic compensating valve.
- Electric storage heater: thermostat at 60 °C (Article 2.6.1.12.).
Water heaters
- T&P valve: sensing element in the top 150 mm, so the tank cannot exceed 99 °C (Article 2.6.1.7.).
- Discharge: at least the NPS of the valve outlet, ending with an air break, never a shut-off valve or cap (Clause 2.6.1.7.(5)(a) and (b), Sentence 2.6.1.7.(7)).
- Thermal expansion: a check valve on the service traps expanding water; add an expansion tank.
- Service: dielectric unions stop galvanic corrosion; rotten-egg odour calls for an aluminum-zinc anode; a dye test finds a leaking flapper.
- Recovery: Btu = gallons x 8.33 x rise; 40 U.S. gal. raised 90 °F with 36 000 Btuh takes about 50 min.
Water treatment
- Devices: point-of-use units conform to CAN/CSA-B483.1 (Sentence 2.2.10.17.(1)).
- Order: sediment, then carbon, then UV last on clear water; the softener feeds the water heater supply.
- Drain: indirect connection (Clause 2.4.2.1.(1)(e)) with an air break at least the pipe NPS and not under 25 mm (Sentence 2.3.3.11.(2)).
- What removes what: softeners take hardness, not bacteria; carbon takes chlorine, taste and odour; UV needs prefiltration; calcite raises low pH.
- Testing: a TDS meter checks RO membranes; a hardness kit checks a softener. Watch for salt bridges, iron-fouled resin and a dirty quartz sleeve.
Treatment calculations
- Hardness: gpg = ppm / 17.12 (342.4 ppm is 20 gpg).
- Softener sizing: Grains = (persons x gallons per day) x (hardness + iron) x days of regeneration; (4 x 60) x (18 + 2) x 4 = 19 200 grains.
- Regeneration: capacity / (gallons per day x gpg): 24 000 / 3 000 = 8 days. The formula sheet is provided at the exam.
Sample questions (5)
1. What is the highest temperature permitted for water leaving a shower head in a dwelling?
- 43 °C
- 49 °C
- 55 °C
- 60 °C
Sentence 2.2.10.7.(4) of the NPC 2020 sets 49 °C as the highest temperature of water discharging from a shower head or into a bathtub. The 43 °C value applies only in healthcare facilities and seniors' residences, 55 °C is not a Code value, and 60 °C is the thermostat setting of an electric storage heater.
2. To what temperature is the thermostat of an electric storage water heater set?
- 43 °C
- 49 °C
- 60 °C
- 99 °C
Article 2.6.1.12. of the NPC 2020 sets the thermostat of an electric storage-type water heater at 60 °C, which limits legionella growth in the tank. The 43 °C and 49 °C values are the shower and bathtub discharge limits, and 99 °C is the tank temperature the temperature-relief valve must prevent from being exceeded.
3. Where is the sensing element of a storage tank's temperature-relief valve located?
- Within the top 150 mm of the tank.
- At the mid-height of the tank.
- Within the bottom 150 mm of the tank.
- On the cold inlet pipe nearby.
Sentence 2.6.1.7.(2) of the NPC 2020 places the sensing element within the top 150 mm of the tank, where the hottest water collects. Mid-height and the bottom of the tank hold cooler water and would react late, and a sensor on the cold inlet pipe does not read the stored water temperature.
4. At what angle must the orifice of a drinking fountain bubbler direct the water?
- Approximately 30° upward
- Approximately 45° upward
- Approximately 60° upward
- Approximately 90° upward
Sentence 2.2.10.9.(1) of the NPC 2020 requires a shielded orifice that directs the water upward at approximately 45°. A flatter 30° stream is not the Code angle, and both a 60° stream and a vertical 90° jet are too steep for a drinking bubbler.
5. Which water closet and seat suit a washroom open to the public?
- Elongated bowl, closed-front seat.
- Round-front bowl, open-front seat.
- Round-front bowl, closed-front seat.
- Elongated bowl, open-front seat.
Article 2.2.2.5. of the NPC 2020 requires an elongated water closet with an open-front seat in a public washroom. The elongated bowl with a closed-front seat fails on the seat, the round-front bowl with an open-front seat fails on the bowl, and the round-front bowl with a closed-front seat fails on both.